DataChangeFilter
Overview
OPC UA Part 4 §7.17 DataChangeFilter lets the client tell the server when to push data:
- Trigger — Trigger Conditions (Status / StatusValue / StatusValueTimestamp)
- DeadbandType — Deadband Type (None / Absolute / Percent)
- DeadbandValue — Deadband Value
The Java side type is MonitoringFilter.Filter, and its three components are MonitoringFilter.Trigger / Enums.DeadbandType / double.
API
| Class / Member | Category | Reading and Writing | Note |
|---|---|---|---|
| new MonitoringFilter.Filter(trigger, deadbandType, deadbandValue) | Structure | — | Construct a filter; trigger=null (default: STATUS_VALUE), deadbandType=null (default: None) |
| MonitoringFilter.Filter.defaultFilter() | Structure | — | STATUS_VALUE + None + 0.0 |
| sub.add(nodeId, onChange, attr, samplingMs, mode, queueSize, discardOldest, filter) | Methods | Write | Overload with a filter, returns an int (mi handle) |
Related Structures (Real Types):
// MonitoringFilter.Trigger / MonitoringFilter.Filter
public enum Trigger { STATUS, STATUS_VALUE, STATUS_VALUE_TIMESTAMP } // Trigger Conditions
public record Filter(Trigger trigger, Enums.DeadbandType deadbandType, double deadbandValue)
public static Filter defaultFilter() // STATUS_VALUE + None + 0.0
// Enums.DeadbandType
public enum DeadbandType { None, Absolute, Percent } // Dead Zone Types
Code Example
import com.darra.opcua.*;
try (OpcUaSession ua = new OpcUaSession("opc.tcp://localhost:4840")) {
ua.connect();
OpcUaSubscription sub = ua.createSubscription(100);
// 1) Absolute Dead Zone 0.5
MonitoringFilter.Filter f1 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS_VALUE, Enums.DeadbandType.Absolute, 0.5);
int mi1 = sub.add("ns=2;s=Temp", null, Enums.AttributeId.Value, 100,
Enums.MonitoringMode.Reporting, 1, true, f1);
// 2) Percentage deadband: 2%
MonitoringFilter.Filter f2 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS_VALUE, Enums.DeadbandType.Percent, 2.0);
int mi2 = sub.add("ns=2;s=Flow", null, Enums.AttributeId.Value, 100,
Enums.MonitoringMode.Reporting, 1, true, f2);
// 3) Status only (deadbandType pass null = None)
MonitoringFilter.Filter f3 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS, null, 0.0);
int mi3 = sub.add("ns=2;s=Comm.Status", null, Enums.AttributeId.Value, 200,
Enums.MonitoringMode.Reporting, 1, true, f3);
sub.onDataChanged.add(args ->
System.out.printf("[mi=%d] %s (%s)%n",
args.monitoredItemHandle, args.valueString, args.status));
}
Implementation Notes
- DataChangeFilter Currently not in effect, SDK Automatic downgrade:
- MI Normal registration, filter disabled, full data reporting
- Filter is cached locally and can be restored even after reconnecting or rebuilding.
- Send a "Diagnostic Warn" event
- The
mode/queueSize/ in the same overloaddiscardOldestare actually effective: non-Reporting routes go throughsetMode, non-default queue routes go throughmodifyItem - Percent Dead Zone Depends on the Target Node's EURange Property
Best Practices
- For analog values, use "Absolute" as the default, such as 0.5°C
- Use "Percent" for wide-range signals
- Digital signals do not require filtering
- Don't make the dead zone too large; experience: 0.1-2%
Cross-Language Comparison
| C# | Python | Java | C++ | Rust | C |
|---|---|---|---|---|---|
| DataChangeFilter | DataChangeFilter | MonitoringFilter.Filter | DataChangeFilter | DataChangeFilter | DarraUa_DataChangeFilter |