Skip to main content

DataChangeFilter

Overview​

OPC UA Part 4 §7.17 DataChangeFilter lets the client tell the server when to push data:

  • Trigger — Trigger Conditions (Status / StatusValue / StatusValueTimestamp)
  • DeadbandType — Deadband Type (None / Absolute / Percent)
  • DeadbandValue — Deadband Value

The Java side type is MonitoringFilter.Filter, and its three components are MonitoringFilter.Trigger / Enums.DeadbandType / double.

API​

Class / MemberCategoryReading and WritingNote
new MonitoringFilter.Filter(trigger, deadbandType, deadbandValue)Structure—Construct a filter; trigger=null (default: STATUS_VALUE), deadbandType=null (default: None)
MonitoringFilter.Filter.defaultFilter()Structure—STATUS_VALUE + None + 0.0
sub.add(nodeId, onChange, attr, samplingMs, mode, queueSize, discardOldest, filter)MethodsWriteOverload with a filter, returns an int (mi handle)

Related Structures (Real Types):

// MonitoringFilter.Trigger / MonitoringFilter.Filter
public enum Trigger { STATUS, STATUS_VALUE, STATUS_VALUE_TIMESTAMP } // Trigger Conditions
public record Filter(Trigger trigger, Enums.DeadbandType deadbandType, double deadbandValue)
public static Filter defaultFilter() // STATUS_VALUE + None + 0.0

// Enums.DeadbandType
public enum DeadbandType { None, Absolute, Percent } // Dead Zone Types

Code Example​

import com.darra.opcua.*;

try (OpcUaSession ua = new OpcUaSession("opc.tcp://localhost:4840")) {
ua.connect();

OpcUaSubscription sub = ua.createSubscription(100);

// 1) Absolute Dead Zone 0.5
MonitoringFilter.Filter f1 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS_VALUE, Enums.DeadbandType.Absolute, 0.5);
int mi1 = sub.add("ns=2;s=Temp", null, Enums.AttributeId.Value, 100,
Enums.MonitoringMode.Reporting, 1, true, f1);

// 2) Percentage deadband: 2%
MonitoringFilter.Filter f2 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS_VALUE, Enums.DeadbandType.Percent, 2.0);
int mi2 = sub.add("ns=2;s=Flow", null, Enums.AttributeId.Value, 100,
Enums.MonitoringMode.Reporting, 1, true, f2);

// 3) Status only (deadbandType pass null = None)
MonitoringFilter.Filter f3 = new MonitoringFilter.Filter(
MonitoringFilter.Trigger.STATUS, null, 0.0);
int mi3 = sub.add("ns=2;s=Comm.Status", null, Enums.AttributeId.Value, 200,
Enums.MonitoringMode.Reporting, 1, true, f3);

sub.onDataChanged.add(args ->
System.out.printf("[mi=%d] %s (%s)%n",
args.monitoredItemHandle, args.valueString, args.status));
}

Implementation Notes​

  • DataChangeFilter Currently not in effect, SDK Automatic downgrade:
    • MI Normal registration, filter disabled, full data reporting
    • Filter is cached locally and can be restored even after reconnecting or rebuilding.
    • Send a "Diagnostic Warn" event
  • The mode / queueSize / in the same overload discardOldest are actually effective: non-Reporting routes go through setMode, non-default queue routes go through modifyItem
  • Percent Dead Zone Depends on the Target Node's EURange Property

Best Practices​

  • For analog values, use "Absolute" as the default, such as 0.5°C
  • Use "Percent" for wide-range signals
  • Digital signals do not require filtering
  • Don't make the dead zone too large; experience: 0.1-2%

Cross-Language Comparison​

C#PythonJavaC++RustC
DataChangeFilterDataChangeFilterMonitoringFilter.FilterDataChangeFilterDataChangeFilterDarraUa_DataChangeFilter

Next Step​