Streaming History Read
Overview
IDE When loading historical data for a trend chart, loading ten-thousand data points all at once List can cause EDT lag OOM.readHistoryStream Returns Stream<OpcUaDataValue> to the business side and process forEach one data point at a time.
Corresponding section of the standard: OPC UA Part 11(Historical Access) §6.5.
API
| Methods | Category | Reading and Writing | Note |
|---|---|---|---|
| ua.readHistoryStream(nodeId, start, end, batchSize) | History | Read | Returns Stream<OpcUaDataValue> |
| ua.readHistoryStream(nodeId, start, end) | History | Read | Same as above; batchSize is fixed at 1000 |
| Parameters | Default | Note |
|---|---|---|
| nodeId | — | Historical Milestone (String) |
| start | — | Start Instant |
| end | — | End Instant |
| batchSize | 1000 | Maximum RPC Points Per Time |
Exception / Null Case: When the value nodeId is null or an empty stringThrow IllegalArgumentException("nodeId"), Does not return an empty stream; start / Returns when start the value is end null or end no later than Stream.empty(); Also returns an empty stream if the underlying read fails.
Code Example
import com.darra.opcua.*;
import java.time.*;
import java.util.Iterator;
import java.util.stream.Stream;
try (OpcUaSession ua = new OpcUaSession("opc.tcp://localhost:4840")) {
ua.connect();
Instant t1 = Instant.now();
Instant t0 = t1.minus(Duration.ofHours(24));
// 1) Render as you go
try (Stream<OpcUaDataValue> s = ua.readHistoryStream("ns=2;s=Temp", t0, t1, 1000)) {
s.forEach(dv -> {
try (dv) {
// Push to Trend Chart
System.out.println(dv.sourceTimestamp() + " = " + dv.variant().asDouble());
}
});
}
// 2) Stream filtering (Each DV must be closed, including those that are filtered out)
long badCount = 0;
try (Stream<OpcUaDataValue> s = ua.readHistoryStream("ns=2;s=Temp", t0, t1, 1000)) {
Iterator<OpcUaDataValue> it = s.iterator();
while (it.hasNext()) {
try (OpcUaDataValue dv = it.next()) {
if (!dv.isGood()) badCount++;
}
}
}
System.out.println("24h 内 " + badCount + " 个坏值");
}
Implementation Constraints
- Currently, readHistory no points are exposed ContinuationPoint; a single call returns RPC all points within the interval (subject to the batchSize limit).
- Business units in large regions can slice their own data
- You must close each DV; otherwise, a memory leak will occur.
Best Practices
- The try-with-resources package: Stream
- For time intervals greater than 1 hour, it is recommended to use outer slices.
- UI Render Throttling: Every 100 refreshes
Cross-Language Comparison
| C# | Python | Java | C++ | Rust | C |
|---|---|---|---|---|---|
| ReadHistoryStreamAsync | read_history_stream | readHistoryStream | ReadHistoryStream | read_history_stream | DarraUa_HistoryStream_New/_Next/_IsEnd/_Free |