Skip to main content

SetMonitoringMode

Each MonitoredItem has 3 monitoring modes:

enum class MonitoringMode : int32_t {
Disabled = 0,
Sampling = 1,
Reporting = 2,
};
ModeServer-Side SamplingServer-Side PushUses
Disabled (0)××Fully stopped (neither sampling nor push)
Sampling (1)✓×Sample, evaluate based on the filter, add the value to the queue MI, but do not publish (the result is reported only after switching back to Reporting).
Reporting (2, Default)✓✓Operating Normally

Default value source: DarraUa_MonitoredItemConfig_Init is initialized monitoring_mode to UA_MI_MODE_REPORTING, AddNode / AddMany / DarraUa_MonitoredItem_Create all start from this initial value, so a new is initially MI set to Reporting.

Prerequisite Reading
  • To cancel your entire subscription (rather than individual issues MI), see below SetPublishingEnabled.
  • To modify the sampling parameters, see Modify.

Batch Cut​

std::vector<Status> SetMonitoringMode(
MonitoringMode mode,
std::vector<uint32_t> const& mi_handles);
// Temporarily suspend all data collection (e.g., during equipment maintenance)
std::vector<uint32_t> all_handles = { h1, h2, h3, h4 };
auto statuses = sub.SetMonitoringMode(MonitoringMode::Disabled, all_handles);

Returns std::vector<Status>, The order is the same mi_handles as ., The success or failure of each individual operation is determined by statuses[i]; mi_handles returns an empty vector when empty. Throws an exception when the entire transmission RPC fails Exception("Subscription_SetMonitoringMode failed", rc), and does not return partial results.

Single MI Cut​

Status SetMode(uint32_t mi_handle, MonitoringMode mode);
sub.SetMode(handle, MonitoringMode::Disabled);   // Pause a certain MI
sub.SetMode(handle, MonitoringMode::Reporting); // Restore

Enable or Disable the Entire Feed (SetPublishingEnabled)​

If you want to cancel the entire subscription (rather than individual issues MI), use SetPublishingEnabled:

sub.SetPublishingEnabled(true);   // Open
sub.SetPublishingEnabled(false); // Pause

Comparison of Three Particle Sizes​

Particle sizeAPIApplicable
Subscribe to the entire seriessub.SetPublishingEnabled(bool)Temporary Service Suspension (Maintenance)
A batch of MIsub.SetMonitoringMode(mode, handles)Some modules are down
Single MIsub.SetMode(handle, mode)Precise Control
Delete Completelysub.Remove(handle) / Subscription destructorI don't want it anymore—ever.

Next Step​