OPC UA → Modbus TCP Bridging

The old device only supports Modbus, while the new device only exposes OPC UA. Write a lightweight bridge: subscribe OPC UA → write to Modbus registers. Use C# + NModbus Example.

Sample Configuration

Dependency​

dotnet add package Darra.OpcUa
dotnet add package NModbus

Complete Code​

using DarraOpcUa_Client;
using NModbus;
using System;
using System.Linq;
using System.Net;
using System.Net.Sockets;
using System.Threading;
using System.Threading.Tasks;

class Program
{
// Mapping Table: OPC UA NodeId → Modbus Register Address
record TagMap(string NodeId, ushort Reg, string Type);

static readonly TagMap[] Mapping = new[]
{
new TagMap("ns=2;s=Boiler1.Temperature", 0, "Float"), // Occupies reg 0/1
new TagMap("ns=2;s=Boiler1.Pressure", 2, "Float"), // Occupy reg 2/3
new TagMap("ns=2;s=Boiler1.IsRunning", 100, "Bool"), // coil 100
};

static async Task Main()
{
const string opcuaEndpoint = "opc.tcp://192.168.1.100:4840"; // Replace with an on-site industrial PC PLC IP
const int modbusPort = 502;

// 1. Start the Modbus Slave TCP
var listener = new TcpListener(IPAddress.Any, modbusPort);
listener.Start();
var factory = new ModbusFactory();
var slaveNet = factory.CreateSlaveNetwork(listener);
var slave = factory.CreateSlave(unitId: 1);
slaveNet.AddSlave(slave);
_ = slaveNet.ListenAsync();
Console.WriteLine($"[OK] Modbus TCP Slave listen on :{modbusPort}");

// 2. Start the Client OPC UA
using var ua = new DarraOpcUa(opcuaEndpoint);
ua.Connect();
Console.WriteLine($"[OK] OPC UA connected to {opcuaEndpoint}");

// 3. Subscription + Type Conversion for Writing to Modbus
using var sub = ua.CreateSubscription(500);
sub.DataChanged += (s, e) =>
{
var map = Mapping.FirstOrDefault(m => m.NodeId == e.NodeId);
if (map == null || e.Status != StatusCode.Good) return;

try
{
switch (map.Type)
{
case "Float":
var f = float.Parse(e.ValueString);
var bytes = BitConverter.GetBytes(f);
slave.DataStore.HoldingRegisters[map.Reg] = BitConverter.ToUInt16(bytes, 0);
slave.DataStore.HoldingRegisters[map.Reg + 1] = BitConverter.ToUInt16(bytes, 2);
break;
case "Bool":
slave.DataStore.CoilDiscretes[map.Reg] = bool.Parse(e.ValueString);
break;
}
Console.WriteLine($" {e.NodeId} = {e.ValueString} -> Modbus[{map.Reg}]");
}
catch (Exception ex) { Console.WriteLine($" map error: {ex.Message}"); }
};

sub.AddMany(Mapping.Select(m => m.NodeId).ToList());

Console.WriteLine("\nBridge 运行中, Ctrl+C 退出...");
await Task.Delay(Timeout.Infinite);
}
}

Code Highlights​

  • Modbus registers are 16-bit; Float Double split into 2 or 4 parts. Byte order (Big/Little Endian, Word Swap) varies by manufacturer; adjust the splitting order according to the byte order of the remote device.
  • The four tables—HoldingRegisters, InputRegisters, Coils, and DiscreteInputs—are independent; before designing the mapping, decide carefully which table to use.
  • For reverse writing (Modbus Master →OPC UA), attach a request reception event on the Modbus side, and call the function within it. ua.Write
  • Multiple devices can be connected to a single listening port unitId; a single process can bridge multiple devices.
  • In this example Modbus TCP, if is required, switch Modbus RTU to a Modbus library that supports the serial port.

Important Notes​

  • HoldingRegisters / InputRegisters / Coils / DiscreteInputs Four separate tables, Think it through before you start designing the map.
  • In this example Modbus TCP, if is required, switch Modbus RTU to a Modbus library that supports the serial port.
Disconnected Sentinel Value

OPC UA: Modbus Register When a Connection Is LostIt will not automatically reset to zero — Upper-level applications may mistakenly assume the data is valid. It is recommended to ua.Events.Disconnected set an "invalid value sentinel" (such as 0xFFFF) in the corresponding register.